Brand Name :Fluke
Model Number :1664FC
Certification :-
Place of Origin :America
MOQ :1
Price :USD120/PC
Payment Terms :L/C, D/A, D/P, Western Union, T/T, MoneyGram
Supply Ability :100
Delivery Time :1DAYS
Packaging Details :Original
Customized support :OEM, ODM
AC voltage Range :500V
Sealing :IP-40
power :AA battery
size :10 x 25 x 12.5 cm
weight :1.3KG
Function :Insulation Pre-test
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

Product overview: Fluke 1664 FC Installation Multifunction Tester

The Fluke 1664 FC Multifunction Installation Tester helps expedite installations

The 1664 FC puts a lot of testing power in your hands to quickly and efficiently test to all local regulations, protect appliances, and share test results in real time over your smartphone.

Test EV charging station RCD type A-EV or RDC-DD DC protection devices

Perform tests on EV charging station DC protection devices using the RCD type B (smooth DC currents) VAR mode, which generates the test currents for RCD type A-EV or RDC-DD acc. to IEC 62955 (6/60/200 mA and ramp <2 to 6 mA ramp). This allows the quick an easy testing of additional 6 mA DC monitors on charging points and can be used in conjunction with the Fluke FEV100 or FEV300.

Protect appliances from accidental damage

The Fluke 1664 FC is the only tester with ""Insulation PreTest"" that stops the insulation test and provides a visual warning if it detects that an appliance is connected to the system under test. This helps you avoid potentially serious and costly mistakes that can cause damage to your customers’ peripheral equipment.

Auto Test reduces test time

Auto Test performs up to seven installation tests in one sequence, ensuring compliance with local installation regulations. This reduces the number of manual connections, thus decreasing the possibility of errors and reducing test time.

Save time and enhance collaboration

Because the 1664 FC is Fluke Connect®-enabled, you can send test results to your smartphone, save them to the cloud, and share measurements in real time with team members through a ShareLive video call. It's the fastest way to let your team see what you see, and to help you get approvals without leaving the field. Fluke Cloud™ storage allows you to retrieve stored results whether you are in the office or in the field to make decisions in real time. You get world-class data protection and can import the data, manage files transferred from instruments, or manually enter data as needed into TruTest™ Software to process and generate certificates quickly and easily. Designed to eliminate the hassle associated with traditional electrical system data management and reporting, TruTest™ Software is an ideal solution for producing easy-to-understand reports for clients.

Other helpful features:

  • Compact, lightweight (less than 1.3 kg) with padded neck-strap to free your hands
  • Rotary dial knob clearly indicates which function is selected, all in one spot with no complex multi-level menus.
  • Offers additional high current loop mode for faster measurements than loop tests with non-trip mode for RCDs
  • Includes Z-max memory for loop tests to support easy evaluation of the highest loop test value
  • Provides unique zero adapter for fast, reliable and accurate test lead and mains cord compensation
  • Performs fast voltage measurement between L-N, L-PE, and N-PE using the mains cord. No need to change measurement connections
  • Measures RCD trip current and trip time in parallel (RCD type AC and A)
  • Measures PEFC or PSC and loop impedance in parallel and displays them together on the dual display
  • Offers ring testing so you can select the required input sockets with soft keys and not have to exchange test leads
  • Uses continuity test currents to measure motor windings
  • Detects raised earth voltages > 50 V with Earth Volt Touchpad, indicating potential dangerous situations
  • Features large display with backlight, clear symbols, and exceptionally wide viewing angle for easy and safe readings
  • Offers extended three-layer memory
  • Specifications: Fluke 1664 FC Installation Multifunction Tester

    Specifications: Fluke 1663 and 1664 FC Installation Multifunction Testers

    AC voltage measurement
    Range 500 V
    Resolution 0.1 V
    Accuracy 45 Hz – 66 Hz 0.8% + 3
    Input impedance 360 kΩ
    Overload protection 660 V rms
    Continuity testing (RLO)
    Range (autoranging) 20 Ω / 200 Ω / 2000 Ω
    Resolution 0.01 Ω / 0.1 Ω / 1 Ω
    Open Circuit Voltage >4 V
    Insulation resistance measurement (RISO)
    Test voltages 50-100-250-500-1000 V
    Accuracy of test voltage (at rated test current) +10%, -0%
    Test voltage 50 V
    100 V
    250 V
    500 V
    1000 V
    Insulation resistance range 20 MΩ / 50 MΩ
    20 MΩ / 100 MΩ
    20 MΩ / 200 MΩ
    20 MΩ / 200 MΩ / 500 MΩ
    20 MΩ / 200 MΩ / 1000 MΩ
    Resolution 0.01 MΩ / 0.1 MΩ
    0.01 MΩ / 0.1 MΩ
    0.01 MΩ / 0.1 MΩ
    0.01 MΩ / 0.1 MΩ / 1 MΩ
    0.01 MΩ / 0.1 MΩ / 1 MΩ
    Test current 1 mA @ 50 kΩ
    1 mA @ 100 kΩ
    1 mA @ 250 kΩ
    1 mA @ 500 kΩ
    1 mA @ 1 MΩ
    Loop and line impedance (ZI)
    Range 10 Ω (Hi current mΩ mode)/20 Ω/200 Ω/2000 Ω
    Resolution 0.001 Ω/ 0.01 Ω/ 0.1 Ω/1 Ω
    Prospective earth fault current, PSC test
    Range 1000 A / 10 kA (50 kA)
    Resolution 1 A / 0.1 kA
    Computation Prospective earth fault current (PEFC) or Prospective short circuit current (PSC) determined by dividing measured mains voltage by measured loop (L-PE) resistance or line (L-N) resistance, respectively.
    RCD testing, RCD types tested
    RCD Type AC¹
    G²,S³
    Model 1663 A4, AC¹, G²,S³
    Model 1664 FC A, AC, B5, S
    Notes ¹Responds to AC
    ²General, no delay
    ³Time delay
    ⁴Responds to pulsed signal
    ⁵Responds to smooth DC signal
    Tripping speed test (ΔT)
    Current settings¹ 10-30-100-300-500-1000 mA – VAR
    10-30-100 mA
    Multiplier x ½, x 1
    x 5
    VAR Mode Type B - 6, 60, 200 mA
    Measurement range RCD Type G 310 ms
    50 ms
    RCD Type S 510 ms
    160 ms
    EV / RDC-DD 6 mA - 10s
    60 mA - 0.3s
    200 mA - 0.1s
    Notes ¹1000 mA type AC only
    700 mA maximum type A in VAR mode
    The VAR Mode at RCD type B (smooth DC currents) generates the test currents acc. to IEC 62955 for RCD type A-EV or RDC-DD (6/60/200 mA and ramp <2 to 6 mA).
    RCD/FI-Tripping Current Measurement/Ramp Test (IΔN)
    Current range 30% to 110% of RCD rated current¹
    <2 mA to 6 mA smooth DC³
    Step size 10% of IΔN²
    Linear rising within 30 s
    Dwell time RCD Type G 300 ms/step
    RCD Type S 500 ms/step
    Measurement accuracy ±5%
    Specified trip current ranges (EN 61008-1) 50% to 100% for Type AC
    35% to 140% for Type A (>10 mA)
    35% to 200% for Type A (≤10 mA)
    50% to 200% for Type B
    Notes ¹30% to 150% for Type A IΔN > 10 mA
    30% to 210% for Type A IΔN = 10 mA
    20% to 210% for Type B
    ²5% for Type B
    ³For RCD type A-EV/RDC-DD acc. to IEC 62955
    Earth Resistance Test (RE)
    Range 200 Ω / 2000 Ω
    Resolution 0.1 Ω / 1Ω
    Frequency 128 Hz
    Output Voltage 25 V
    Phase Sequence Indication
    Icon Original And New Fluke 1664FC Multifunction Installation Tester US Power Cord MultifunctionTester Phase Sequence indicator is active.
    General Specifications
    Size (L x W x H) 10 x 25 x 12.5 cm
    Weight (incl. batteries) 1.3 Kg
    Battery size, quantity Type AA, 6 ea.
    Sealing IP-40
    Safety Complies with EN/IEC 61010-1 and EN/IEC 61010-2-034
    Overvoltage CAT III / 500V; CAT IV 300V
    Performance EN61557-1 to EN61557-7 and EN61557-10

Inquiry Cart 0