Mengchuan Instrument Co,Ltd.

We have excellent and experienced foreign trade team and other teams to provide you with the best and professional services. Our products are sold all over the world as best-selling products and high

Manufacturer from China
Verified Supplier
4 Years
Home / Products / Programmable Logic Controller /

Miniature PLC Logic Controller Thermocouple Input Integrated PLC 220v ac

Contact Now
Mengchuan Instrument Co,Ltd.
Visit Website
City:wenzhou
Province/State:zhejiang
Country/Region:china
Contact Person:MissYANG
Contact Now

Miniature PLC Logic Controller Thermocouple Input Integrated PLC 220v ac

Ask Latest Price
Brand Name :xinje
Model Number :XD3-22T4TC-E
Certification :CCC
Place of Origin :CHINA
MOQ :1
Price :$98-110/pc
Payment Terms :L/C, T/T, Western Union
Supply Ability :1000/PC/MONTH
Delivery Time :14 Work days
Packaging Details :Carton (standard original package)
Processing speed :0.02~0.05us
User program capacity ※1 :256kB
Control precision :±0.5℃
Resolution :0.1℃
Comprehensive accuracy :1%(Relative maximum)
Conversion speed :80ms/1 channel
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

XD3-22T4TC-E PLC

XD3 series special model integrates logic control and thermocouple input. Digital value input: 8 points (NPN optocoupler isolation), digital value output: 14 points (transistor type); thermocouple signal input: 4 points

Product features

XD3 series special model integrates logic control and thermocouple input.

Digital value input: 8 points (NPN optocoupler isolation), digital value output: 14 points (transistor type)

Thermocouple signal input: 4 points

Power specification: AC220V

Support 2 channels of AB phase input

Support 2 channels of high-speed counting (10kHz)

Support MODBUS and X-NET communication

High cost performance, greatly saving space

Model list

Model Function
XD3-22T4TC-E

8-channel NPN type digital value input, 14-channel

transistor output, 4-channel thermocouple signal input

Function table

Series USB port RS232 port RS485 Free communication Extension module Extension BD Left extension ED High speed counting channel Pulse output External interrupt
Increase mode AB phase
XD3-22T4TC × 2 × × × 2 2 2

6

General Specifications

Item Specification
Isolation Above DC 500V 2MΩ
Anti-noise Noise voltage 1000Vp-p 1us pulse 1 minute
Air No corrosive, flammable gas
Ambient temperature 0℃~60℃
Ambient humidity

5%~95% (no condensation)

USB port -
COM1 RS232(default X-NET protocol), connect upper PC for programming and debug
COM2 RS232(default Modbus), connect upper PC or HMI for programming and debug
COM3 RS485, connect to intelligent instrument and frequency inverter
Installation Use M3 screws or DIN rail to fix
Ground (FG) The third type grounding (do not grounding with strong power system)

Functional Specifications

Item Specification
Program execution mode Loop scan mode
Programming mode Command and ladder chart
Processing speed 0.02~0.05us
Power-off retentive FlashROM and 3V lithium battery
User program capacity ※1 256kB

I/O

points

※2

Total points 22 points
Input points 8 points X0~X7
Output points 14 points Y0~Y15
Internal coils (X)※3 1280 points: X0~X77, X10000~X11777, X20000~X20177, X30000~X30077
Internal coils (Y) ※4 1280 points: Y0~Y77, Y10000~Y11777, Y20000~Y20177, Y30000~Y30077

Internal coils

(M, HM)

11008 points M0~M7999【HM0~HM959】※5
Flow (S) 1152 points S0~S1023【HS0~HS127】
Timer (T) Points 712 points T0~T575【HT0~HT95】
Precise timer ET0~ET39
Spec

100ms timer: 0.1~3276.7s

10ms timer: 0.01~327.67s

1ms timer: 0.001~32.767s

Counter (C) Points 712 points C0~C575【HC0~HC95】
High speed counter HSC0~HSC39
Spec

16-bit counter: K0~32,767

32-bit counter: -2147483648~+2147483647

Data register (D) 11548 words D0~D7999【HD0~HD999】※5
Special use ※6 SD0~SD2047 【HSD0~HSD499】※5

FlashROM register

(FD)

8192 words FD0~FD6143
Special use ※6 SFD0~SFD1999
Special encrypted register FS0~FS47
Special coil for WAIT instruction 32 points SEM0~SEM31
High speed processing ability High speed counter, pulse output, external interruption
Password protection 6-bit ASCII
Self-diagnose function

Power on self-check, monitor timer, grammar check

Notes:
※ 1: User program capacity refers to the maximum program capacity during secret download.
※ 2: I / O points refer to the number of terminals that users can access and output signals from the outside.
※ 3: X refers to the internal input relay, and X exceeding I points can be used as intermediate relay.
※ 4: y refers to the internal output relay. Y exceeding O points can be used as an intermediate relay.
※ 5: [ ] flag, which is the default power-off holding area and cannot be changed.
※ 6: Special use refers to the special purpose register occupied by the system, which can not be used for other purposes.
※ 7: The numbers of input coils and output relays / transistors are octal numbers, and the numbers of other memories are decimal numbers.
※ 8: I / O without real connection with peripheral equipment can be used as fast internal relay.

Function configuration table:

Item Contents
Analog input K, S, E, N, B, T, J, R types of thermocouple
Measuring temperature range Type K 0℃~1300℃
Type S 0℃~1700℃
Type E 0℃~600℃
Type N 0℃~1200℃
Type B 0℃~1800℃ (display 0 below 250℃)
Type T 0℃~400℃
Type J 0℃~800℃
Type R 0℃~1700℃
Digital output range

0~max measuring temperature value ×10 (take type K as an example, the digital output range is 0~13000)

Signed 16 bits, binary

Control precision ±0.5℃
Resolution 0.1℃
Comprehensive accuracy 1%(Relative maximum)
Conversion speed 80ms/1 channel

Note:

(1) When there is no signal input, the channel data is - 1.

(2) Connect thermocouples according to actual needs.

(3) The enclosure of the equipment installed by the thermocouple must be grounded.